Related matters about the shutdown of the steam boiler

Related matters about the shutdown of the steam boiler

Date of issue:2015-12-15 00:00 Source:http://rizhaolimingyuming.cn Click:

Normal shutdown is the planned shutdown of the furnace due to load reduction, maintenance and other reasons, which is called normal shutdown.


  Method: Follow the operating procedures


  ① Reduce the load gradually.


 ?、?Stop supplying fuel to the furnace.


  ③ Stop the induced draft fan.


 ?、?After stopping the steam supply, close the isolation valve connected to the main pipe.


 ?、?When the temperature of the boiler water drops below 70℃, the boiler water can be discharged.


  Steam boiler shutdown due to accident


  Stop the furnace immediately when one of the unlisted situations is encountered during operation:


 ?、賂he boiler water level is lower than the visible edge of the lower part of the water level gauge.


 ?、贑ontinuously increase water supply and adopt other measures, but the water level continues to drop.


 ?、跿he water level exceeds the highest visible water level, and the water level is still not visible after the water is released.


 ?、蹵ll feedwater pumps fail or the feedwater system is faulty, and no water can enter.


 ?、軦ll water level gauges or safety valves are out of order.


 ?、轇oiler element damage endangers the safety of operating personnel.


 ?、逿he burning equipment is damaged, the furnace wall collapses or the frame is burned red, etc., which seriously threaten the safe operation of the boiler.


  ⑧ Other abnormal conditions endanger the safe operation of the boiler.


  Operation steps for emergency shutdown of steam boiler


 ?、賁top coal and air supply immediately to reduce induced air (or stop).


 ?、赨nload the remaining coal in the furnace at the fastest speed.


 ?、?Completely isolate the boiler from the main pipe, open the air valve, safety valve and trap to quickly discharge steam and reduce pressure.


 ?、躉pen the furnace door and the ash door to promote air dredging and speed up cooling.


 ?、?For water shortage accidents, it is strictly forbidden to enter the pot water, and it is not allowed to open the valve to exhaust steam and reduce the pressure to prevent the accident from expanding.


⑥ If the boiler is shut down due to a full water accident, the water supply should be stopped immediately, the flue baffle should be closed, the combustion should be reduced, the drain valve should be opened to drain the water, and the water level should be appropriately lowered. At the same time, open the main steam pipe sub-cylinder and the trap valve on the main pipe. Prevent a large amount of steam from carrying water and water shock in the pipeline.


Related labels:環(huán)保鍋爐

Liao ICP No. 13002650 Copyright: Yingkou Yongde Heavy Industry Co., Ltd.

Technical support: Yingkou Zhongchuang Network Technology Co., Ltd.


Electricwords:0417-3299986

            18241729088

Address: No. 26, Yuanjiao 3rd Street, Xishi District, Yingkou City, Liaoning Province (near Liaohe Bridge)

Website: rizhaolimingyuming.cn

1615445058751615.png

QR code

成人看片黄a免费看-亚洲精品无码专区久久同性男-精品无码久久久久久久动漫-精品久久久久久久久亚洲偷窥女厕-18成人片黄网站www